  • According to ISO9705 of building materials fire prevention performance standards, this fire test machine control platform provides independent gas analysis, including heat release rate and other related tests required for related instruments, such as paramagnetic oxygen sensor, CO2/CO measuring instrument, He-Ni laser smoke density measurement and control system, etc.
  • Full-scale room corner test methods for the surface of the article use the same principle as the cone calorimeter and SBI test methods that are based on oxygen consumption.
  •  The method is to simulate the corner of the fire scene as a standard test condition, and installation of a test sample entirely according to actual use, the test results apply only to specific sample installation, it is one of the most reliable standard test methods. 
  • In the corner fire test, in accordance with the requirements of ISO9705, the measured material mounted on the inner walls of the room (at the top is not installed). 
  • Using propane burners as a radiation source, the measurement of heat release rate, temperature, heat release, flashover time, CO2 /CO, and other parameters, for which the most important are the heat release rate and the flashover time.
Standards
• ISO 9705: Large Box test surface of the product
• ISO 13784-1: plywood building systems Reaction to fire test
• ASTM E 1537: Standard upholstered furniture flame test method
• ASTM E 603: Standard guidance corner combustion experiments
Gas sampling and analysis system
1, Gas sampling system includes an annular sampler probe, suction pump, particulate filter, a cold trap, exhaust valve, water filters, and CO2 filter.
2, Three filters; Minimum filtration accuracy is 0.5um.
3, Freezing cold trap; air-conditioning compressor refrigeration systems; controlling the temperature in 0 ~ 5ºC.
4, Suction pump, Flowrate is 33L/min, vacuum is 700mmHg, and pressure is 2.5 bar.
5, Drying cylinder, which filters the water and impurities.
6, The flow controller controls the inspiratory airflow.
7, The sampler has 12 holes, and gas flow in the opposite direction, these hold a built-in dust filter and 685mm from hoods.
8, Paramagnetic oxygen analyzer, the range is 0-25%; linear response; imports Britain Servomex oxygen sensor.
Smoke system
1, 0.5W HE-NE laser source.
2, Thorlabs optically detector.
3,Motor driven5 class automatically calibration device with of 0%, 25%, 50%, 75%, 100% transmittance filters.
4, One touch calibration system in software with digital and curve display.
DAQ system
1, 16bit data acquisition module.
2, Digital communication between computer and DAQ module.
3, Labview-based application software on DAQ and data analysis.
Operating system
1, Labview-based application system, easy and precise to operate and control.
2, Test status, and calibration status are displayed onscreen.
3, the Device status is displayed on the screen and indicators on the panel.
4, Transducer data, process parameters, and test results are displayed on screen via digital and curve.
5, Test and calibration procedure auto executed by PLC program.
6, Device can be controlled via both the application screen and a control panel.
7, PC and PLC communicate with a digital protocol that is safe and robust.
Technical Specifications
1, Paramagn etic oxygen analyzer, the concentration range is 0~25%, an oxygen analyzer is a linear response, Britain Servomex oxygen sensor; 10% to 90% response time of less than 12s; output noise does not exceed 50ppm; Reproduce the measured values lower than 100ppm,
2, Infrared CO2 analyzer range: 0 to 10%;accuracy of ± 0.01%;
3, The compressor works: cold trap: 0 to 5 degrees;
4, Import diaphragm pump, flow rate: 33 l / min
5, The standard detector color accuracy ± 5%, output linearity (transmission) <1%, absolute permeability <1%;
Test Data
1, Heat Release Rate (HRR),
2, Total Heat Release (THR),
3, Efficiency Heat Release (EHR),
4, Smoke Production Rate (SPR),
5, Time to Ignite (TTI),
6, Time to flameout,
7, Oxygen Consumption Rate,
8, CO2 Production Rate,
9, CO Production Rate(optional)

Place of Origin CHINA
Brand Name AI
Model Number AIC-9705
Certification ISO
Size 11,725(W)x4,000(D)x4,750(H)mm
Console Size 600(W)×750(D)×1800(H)mm
Power supply AC 220V, 50/60Hz, 15A (control), AC 380V, 60Hz, 50A(drive)
Weight About 7,500kg(Cabinet), 130kg(Control panel)
Exhaust Minimum 3.5m2/s(Measuring), Minimum300m2/min(Exhaust)
Other requirements CO(0.8%)/CO2(8%), Compressed gas, Vacuum cleaners, Computers, Propane gas, Heptane gas, Nitrogen
Instructions Provided

  • The test room is built with a density of 700kg / m³-A1 class fireproof material.
  • The internal dimensions of the room are 3.6M X 2.4M X 2.4M
  • The gate size: 0.8M (W) X2.0M (H)
  • Sandbox burner with propane gas and equipped with emergency shut-off devices.
  • Automatic ignition system to automatically record experimental data;
  • Independently movable time to display units.
  • 10kV spark ignition, a cease-fire with safety devices. Fire extinguishing drainage system design.
  • The full-scale room corner test machine is equipped with a staircase for easy maintenance of exhaust pipes.